For single-pipe installation with monoblock burners and systems according to DIN 4755 BI.2 and TRD 411 or 604. These fuel oil air-separation units are to be considered as a component of a burner unit and designed for a max. pressure of 5 bar.

Technical Data:

Details and applications

  • Medium: fuel oil EL and L
  • Internal setting: max. 45 °C

Basic design A for supply pressure

by means of separate feed pump through the ring main present or tank situated higher up.

For single-pipe oil installation of automatic oil fuel with fuel oil EL suitable for systems to DIN 4755 or TRD.

Functional description:

Design according to scheme A (with supply pressure on T connection)

The burner pump shall supply the oil via a ball valve , filter, adapter for oil meter (or optionally integrate oil meter ) and vessel in the single pipe system, i.e. in T connection, only the fuel oil used by the boiler flows. In T1 and R connections, on the other hand, the full intake flow of the burner pump flows. The bypass oil R coming from the burner is directed via the vessel back to the burner. The air arising as a result may be vent by manual ventilation.

Optionally, automatic vent by a float air vent is also possible.

This unit is designed for supply pressure of 1 – 5 bar.

Other designs (e.g. for suction operation or deviating accessories) may be provided on request.

Illustration

Packing list

  1. Weld neck flange
  2. Connection flange PN 16
  3. Ball valve PN 16
  4. Filter
  5. Adapter for oil meter
  6. Vessel
  7. Overflow valve as safety valve
  8. Oil pan with fastening
  9. Manometer
  10. Ball valve for Manometer and ventilation

Summary table

Size Burner flow
on T l/h
Burner pump
max. l/h
Supply
connection
T
Burner
connection
R + T1
Vessel
capacity
litres
Dimensions Item No.
LBA 600 A 10 – 200 600 DN 15 G 3/4″ 5 1050 x 360 480060
LBA 1200 A 10 – 400 1200 DN 15 G 3/4″ 18 1400 x 500 480120
LBA 2400 A 30 – 1000 2400 DN 20 G 1″ 30 1400 x 500 480240
LBA 3000 A 75 – 2000 3000 DN 25 G 1″ 30 1400 x 500 480300

OPTION FOR AIR-SEPARATION UNIT SERIES LBA-A

Summary table for Option LBA-A

Item Brief
description
Name LBA 600
Item no.
LBA 1200
Item no.
LBA 2400
Item no.
LBA 3000
Item no.
5.1 HZ Oil meter VZO 15 to 25 RC 700312 700312 700320 700326
5.2 RV Pulse generator RV = 0.1 for VZO 15; Pulse generator RV = 1 for VZO 700313 700313 700321 700327
5.3 IN Pulse generator IN = 0.1 for VZO 15; Pulse generator IN = 1 for VZO 700315 700315 700322 700328
21 EE End position switch, including bracket, 230 V/50 Hz 820730 820730 820730 820730
23.1 G/SE Automatic float air vent for optimum ventilation 820212 820212 820212 820212
25 EF Single filter G 3/4″ / PN10, 100µ/td>

820022 820022
25 EF Single filter G 1″ / PN6, 100µ 842950 842950
26 M Piston solenoid valve, G 1/2″– DN 10, DIN & TÜV tested 0820257 M 0820257 M
26 M Piston solenoid valve, G 3/4″– DN 15, DIN & TÜV tested 0820258 M
26 M Piston solenoid valve, G 1″– DN 15, DIN & TÜV tested 0820259 M
29 S Pressure switch G 1/2″, 230 V/50 Hz, adjustment range: 0.5 – 6 bar 0720672 M 0720672 M 0720672 M 0720672 M
30 DK Double ball valve combination 821110 821112 821112 821114
35 LH Leakage detector integrated into oil pan, type LMW (sensor 1.5 m) 0720705-1 0720705-1 0720705-1 0720705-1
36 DM Pressure-regulator valve 0.2–2.5 bar 0821185 M 821186 821187 821188
7 DA Pressure equalisation as safety valve with component test
possible at an additional cost, set to 3 bar with sealing cap
820372 820372 820372 820372

Need additional infos? Please contact us

Jochen Twellaar

+49 (0) 721/95618-23

twellaar@hptechnik.com

Joachim Rau

+49(0) 721/95618-25

rau@hptechnik.com