Single units HSPE series
This hp oil supply is for fireplaces that are far or high from the storage tank. The suction units can handle underpressures up to -0.9 bar, which is 9 m geodetic height or even up to 200 m suction pipe length.
Model | Discharge l/h |
ave. 1) Extraction quantity l/h |
Motor power 2) | Item No. | max. burner connections |
Weight Kg approx. |
||
230 V Alternating current | 400 V Rotary current | HSPE | additional burner connections | |||||
HSPE 30 – Standard – 6042 | 80 | 50 | 0,18 kW | – | 430002 | 430200 | 2 | 25 |
HSPE 60 – 6044 | 160 | 120 | 0,18 kW | – | 430008 | 430200 | 4 | 8 |
HSPE 200 – 6045 | 300 | 200 | 0,18 kW | – | 430014 | 430201 | 4 | 0 |
HSPE 200 – 6047 | 600 | 400 | 0,18 kW | – | 430024 | 430201 | 4 | 0 |
HSPE 700 BHP | 1000 | 700 | – | 0,75 kW | 430030 | 430202 | 5 | 145 |
HSPE 700 BHM | 1500 | 1000 | – | 0,75 kW | 430038 | 430202 | 5 | 145 |
HSPE 700 BHG | 2000 | 1500 | – | 0,75 kW | 430040 | 430202 | 5 | 145 |
HSPE 1500 BHGP | 3000 | 2200 | – | 1,10 kW | 430048 | 430210 | 5 | 200 |
Leakage detector in plug-in casing Type LMS for 230 V (for description see page 83). | ||||||||
Leakage detector in control system integrated Type LMP for 230/400 V | ||||||||
From HSPE 30, additional spill protection to VbF or WHG permitted | 720713 | |||||||
For further dimensions see page 52. |
The HSPE 30 and 60 may be supplied with 4 feet, as desired (see price list).
Maintenance: The HSPE suction units are maintenance-free, only the suction filter is to be cleaned regularly.
All models installed, tested and registered suitable for heating oil EL, to DIN/EN 12514-1 and DIN 4755 part 2.
1) As the discharge basically depends on the viscosity of the medium, the suction length, the suction resistance, the suction height, the pipe diameter and the temperature, a technical fine-tuning is required in each individual case.
2) Motor voltages 230 V or 230/400 V, 50 Hz
hp-Suction units Series HSP Based on empirical determination with heating oil EL at 20 °C.
These performance curves are based on tests with optimum pipe flow and may only be considered as guidelines. Not all usage cases can be derived from them. Copying, duplication or forwarding to third parties requires our written permission.
Need additional infos? Please contact us