Search
Close this search box.

Oil day tank

The oil operating tanks may be filled with an external supply pump. Using a freely programmable µCon III model control system and a relevant capacitive level recording system, the fill levels in the operating tanks are regulated. The gas emissions of the medium when conveying will be carried away by an air discharge port. This ensures a bubble-free supply of the consumption points with fuel. The filling pump(s) can be controlled by the available µCon III control system. However, it is also possible to activate them using a separate pump control system. It is designed and tested to DIN EN 12 514 – 1.

An ideal place of installation of the operating tank is in the immediate vicinity of the consumption points.

Technical Data:

Details und Anwendungen

  • Operating tanks of: Al or sheet steel (day fuel tank)
  • Level control system (230 V or 400 VAC) with leakage detector
  • Level sensor
  • Filling port
  • Air discharge port
  • Consumer connection
  • Solenoid valve
  • Oil pan
  • Spill protection
  • Supply line with shut-off, filter and pressure monitor
  • Spill protection to § 63 WHG
  • Oil operating tanks for emergency power diesel units
  • Oil operating tanks for block heat and power plants
  • Oil operating tanks for burner supply
Model Tank Volume / litres during switching Tank dimensions Filling port
connection
Oil pan Item No.
Model max. capacity in l
min / In max / Out Overfilled / l Length Width Height
ÖVB 70 NG 70 63 9 55 60 605 465 380 DN 15 800 x 600 0420 500
ÖVB 160 E 160 160 50 130 150 810 640 560 DN 20 1160 x 745 0420 510
ÖVB 250 E 250 280 50 130 150 1010 700 580 DN 25 1300 x 1100 0420 520

Other sizes on request
For air discharge port connection and extraction connections, as for suction unit, see table on

Schema

1 Pump unit (single or double)
2 Oil operating tank
2.1 Tank control system
2.2 Air discharge port
2.3 Manometer

2.4 Ball valve
2.5 Pressure switch
2.6 Oil filter
2.7 Nonreturn valve
2.8 Oil pan

2.9 Leakage detector
2.10 Level sensor
2.11 Spill protection
2.12 Bypass connection
2.13 Consumer connection

Need additional infos? Please contact us

Jochen Twellaar

+49 (0) 721/95618-23

twellaar@hptechnik.com

Joachim Rau

+49(0) 721/95618-25

rau@hptechnik.com